TROUBLE CONDITION:

Trouble light flashing and panel beeping.

  1. Press the Acknowledge Button on the panel.
  2. Read LCD screen fort trouble location or look for indicator lights on panel.
  3. If issue is not resolvable, contact Enterprise at 866-620-5504.

Note: Pressing the Acknowledge Button will silence the panel but if the panel is monitored by an
outside service they will continue to receive these trouble calls unless you request the trouble
calls are disregarded.

SUPERVISORY CONDITION:

Supervisory light flashing and panel beeping.

  1.  Press the Acknowledge Button on the panel.
  2. Read LCD screen fort trouble location or look for indicator lights on panel.
  3. Supervisory conditions are often related to other systems within the building, you may have to investigate:
    1. Sprinkler system control valves or air compressor/antifreeze systems.
    2. Power failure to elevator, shunt trip and related systems.
    3. HVAC duct smoke detection systems, or other dirty detectors.
    4. Furnace/Air Conditioning.